The best response times are obtained at the
limit of the instability. If no stable position
can be obtained, try disconnecting or repla-
cing the ST2 jumper (normal/fast).
h) Check LAM operation : ST5 closed.
i) Vary the frequency (speed) around 48 or
58 Hz according to the operating frequency,
and check the change in voltage from that
observed previously (~ 15%).
j) Readjust the speed of the unit to its rated
no-load value.
Adjustments in parallel operation
Before any intervention on the alterna-
tor, make sure that the speed droop is
identical for all engines.
k) Preset for parallel operation (with C.T.
connected to S1, S2)
- Potentiometer P1 (quadrature droop) in
centre position.
Apply the rated load (cos ϕ = 0.8 inductive).
The voltage should drop by 2 to 3%. If it in-
creases, check that V and W and also S1
and S2 have not been reversed.
l) The no-load voltages should be identical
for all the alternators intended to run in pa-
rallel.
- Couple the machines in parallel.
- By adjusting the speed, try to obtain 0 KW
power exchange.
- By altering the voltage setting P2 on one of
the machines, try to cancel (or minimise) the
current circulating between the machines.
- From now on, do not touch the voltage set-
tings.
m) Apply the available load (the setting is only
correct if a reactive load is available)
- By altering the speed, match the kW (or di-
vide the rated power of the units proportionally)
- By altering the quadrature droop potentiome-
ter P1, match or divide the currents.
10
Installation and maintenance
R438
A.V.R.
3.2.2 - Max. excitation setting (excitation
ceiling)
Max. excitation
P5
P3
P2
Static adjustment of the current limit,
potentiometer P5 (factory setting: 7.5 A,
fuse rating: 8 A - 10 seconds).
The maximum factory setting corresponds
to that of the excitation current required to
obtain a 3-phase short-circuit current of
approximately 3 IN at 50 Hz for industrial
power, unless otherwise specified(*).
A static method can be used to reduce this
value or adapt the Isc to the actual operating
power (derated machine), which is safer for
the
Disconnect power supply wires X1,X2 and
Z1,Z2
(0-110V-220V-380V) on the alternator.
Connect the mains power supply using a
transformer
(X1,X2 : 48V). Install a 10A D.C. ammeter
in series with the exciter field. Turn P5 fully
anti-clockwise and activate the power
supply. If there is no output current from the
AVR, turn potentiometer P2 (voltage)
clockwise until the ammeter indicates a
stable current. Switch the power supply off,
then on again, turn P5 clockwise until the
required max. current is obtained (no more
than 8 A).
236/242
Depending on
the mains frequency
ST3
48 V
X2
50Hz 60Hz
Z1
X1
Z2
E+
R 438
E-
0V
110 V
220 V
ST4
380 V
110/220/380 V
Voltage
alternator
and
and
the
(200-240V)
3971 en -
2010.11 / f
Main
(50/60 Hz supply)
A
Field
+
~ 5 ohms
A
10 A CC/DC
D
the
installation.
voltage
reference