Installation

Mounting/Installation

Install the ANN-LED Module as described in the documentation supplied with the annunciator.

ANN-LED Board Layout and Connection to FACP

Figure 2.27 illustrates the ANN-LED board wiring connections to the FACP.
TB3
2.8.7 ANN-RLY Relay Module
The ANN-RLY relay module provides 10 programmable Form-C relays when used with a compat-
ible FACP.

Specifications

Operating Voltage: 24 VDC
Max. Current:
Alarm: 75 mA
Standby: 15 mA
Relay Contact Ratings:
2 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Operating Temperature: 32
For indoor use in a dry location only
54
ANN-BUS (ID#)
Address DIP switch
FACP
-24 VDC
+24 VDC
Primary ANN-BUS
Figure 2.27 ANN-LED Board Layout and Connection to FACP
o
F to 120
MS-5UD & MS-10UD Series Manual — P/N 52626:C2 1/24/2012
o
o
o
F (0
C to 49
C)
ANN-BUS Devices
ANN-LED