Typical power cable sizes

The table below gives copper and aluminum cable types with concentric copper shield for
the drives with nominal current. For the cable sizes accepted by the drive cabinet lead-
throughs and connection terminals, see page 184.
Drive type
U
= 400 V
N
ACS880-07-0105A-3
ACS880-07-0145A-3
ACS880-07-0169A-3
ACS880-07-0206A-3
ACS880-07-0246A-3
ACS880-07-0293A-3
ACS880-07-0363A-3
ACS880-07-0430A-3
ACS880-07-0505A-3
ACS880-07-0585A-3
ACS880-07-0650A-3
ACS880-07-0725A-3
ACS880-07-0820A-3
ACS880-07-0880A-3
UN = 500 V
ACS880-07-0096A-5
ACS880-07-0124A-5
ACS880-07-0156A-5
ACS880-07-0180A-5
ACS880-07-0240A-5
ACS880-07-0260A-5
ACS880-07-0302A-5
ACS880-07-0361A-5
ACS880-07-0414A-5
ACS880-07-0460A-5
ACS880-07-0503A-5
ACS880-07-0583A-5
ACS880-07-0635A-5
ACS880-07-0715A-5
ACS880-07-0820A-5
UN = 690 V
ACS880-07-0061A-7
ACS880-07-0084A-7
ACS880-07-0098A-7
ACS880-07-0119A-7
ACS880-07-0142A-7
ACS880-07-0174A-7
ACS880-07-0210A-7
Frame
size
Cu cable type
2
mm
R6
3×50
R6
3×95
R7
3×120
R7
3×150
R8
2 × (3×70)
R8
2 × (3×95)
R9
2 × (3×120)
R9
2 × (3×150)
R10
3 × (3×95)
R10
3 × (3×120)
R10
3 × (3×150)
R11
3 × (3×185)
R11
3 × (3×240)
R11
3 × (3×240)
R6
3×50
R6
3×95
R7
3×120
R7
3×150
R8
2 × (3×70)
R8
2 × (3×70)
R9
2 × (3×120)
R9
2 × (3×120)
R9
2 × (3×150)
R10
3 × (3×95)
R10
3 × (3×95)
R10
3 × (3×120)
R10
3 × (3×150)
R11
4 × (3×185)
R11
4 × (3×240)
R6
3×25
R6
3×35
R7
3×50
R7
3×70
R8
3×95 3)
R8
3×120 3)
R9
3×185
Guidelines for planning the electrical installation 73
1)
IEC
Al cable type
2
mm
3×70
3×120
3×150
3×240
2 × (3×95)
2 × (3×120)
2 × (3×185)
2 × (3×240)
3 × (3×150)
3 × (3×185)
3 × (3×240)
4 × (3×185)
4 × (3×240)
4 × (3×240)
3×70
3×95
3×150
3×185
2 × (3×95)
2 × (3×95)
2 × (3×185)
2 × (3×185)
2 × (3×240)
3 × (3×150)
3 × (3×150)
3 × (3×185)
3 × (3×240)
4 × (3×185)
4 × (3×240)
3×35
3×50
3×70
3×95
3×120
2 × (3×70)
2 × (3×95)
2)
US
Cu cable type
AWG/kcmil per phase
1
2/0
3/0
250 MCM
300 MCM
2 × 3/0
2 × 4/0
2 × 250 MCM
2×500 MCM or 3×250 MCM
2×600 MCM or 3×300 MCM
2×700 MCM or 3×350 MCM
3×500 MCM or 4×300 MCM
3×600 MCM or 4×400 MCM
3×600 MCM or 4×400 MCM
1
2/0
3/0
250 MCM
300 MCM
2 × 2/0
2 × 250 MCM
2 × 250 MCM
2 × 250 MCM
2×400 MCM or 3×4/0
2×500 MCM or 3×250 MCM
2×600 MCM or 3×300 MCM
2×700 MCM or 3×350 MCM
3×500 MCM or 4×300 MCM
3×600 MCM or 4×400 MCM
4
3
2
1/0
2/0
4/0
300 MCM