Implementing a bypass connection

If bypassing is required, employ mechanically or electrically interlocked contactors
between the motor and the drive and between the motor and the power line. Make sure
with interlocking that the contactors cannot be closed simultaneously.
WARNING! Never connect the drive output to the electrical power network. The
connection may damage the drive.

Example bypass connection

An example bypass connection is shown below.
Q1
Drive main switch
Q4
Bypass circuit breaker
K1
Drive main contactor
K4
Bypass contactor
K5
Drive output contactor
Guidelines for planning the electrical installation 83
S11
Drive main contactor on/off control
S40
Motor power supply selection (drive or direct-on-
line)
S41
Start when motor is connected direct-on-line
S42
Stop when motor is connected direct-on-line
-
-