ABB ACS880-07 Hardware Manual page 221

Industrial drives (45 to 630 kw, 50 to 700 hp)
Hide thumbs Also See for ACS880-07:
Table of Contents

Advertisement

Frame
SIL
U
= 525...690 V
1
R6 to R9
3
R10, R11
3
Frame
PL
U
= 380...500 V
1
R6
e
R7
e
R8
e
R9
e
R10
e
R11
e
U
= 525...690 V
1
R6 to R9
e
R10, R11
e
* according to Table E.1 in EN/ISO 13849-1
This temperature profile is used in safety value calculations:
670 on/off cycles per year with
1340 on/off cycles per year with
30 on/off cycles per year with
32 °C board temperature at 2.0% of time
60 °C board temperature at 1.5% of time
85 °C board temperature at 2.3% of time.
The safety data is calculated for redundant use, and does not apply if both channels
are not used.
The STO is a type A safety component as defined in IEC 61508-2.
Relevant failure modes:
The STO trips spuriously (safe failure)
The STO does not activate when requested
A fault exclusion on the failure mode "short circuit on printed circuit board" has been
made (EN 13849-2, table D.5). The analysis is based on an assumption that one
failure occurs at one time. No accumulated failures have been analyzed.
STO reaction time (shortest detectable break): 1 ms
STO response time: 2 ms (typical), 5 ms (maximum)
Fault detection time: Channels in different states for longer than 200 ms
Fault reaction time: Fault detection time + 10 ms
STO fault indication (parameter 31.22) delay: < 500 ms
STO warning indication (parameter 31.22) delay: < 1000 ms
SC
PFH
d
(1/h)
3
3.84E-09 (3.84 FIT)
3
3.91E-09 (3.91 FIT)
EN/ISO 13849-1
CCF
MTTF
d
(%)
(Years)
80
3847
80
3847
80
1374
80
1374
80
18774
80
18774
80
1374
80
18774
T = 71.66 °C
T = 61.66 °C
T = 10.0 °C
Safe torque off function 221
IEC 61508
HFT
SFF
(%)
1
95.04
1
99.63
DC*
Cat.
(%)
> 90
3
> 90
3
> 90
3
> 90
3
> 90
3
> 90
3
> 90
3
> 90
3
Lifetime
PFD
(Years)
(T1 = 2 a)
20
1.56E-4
20
3.43E-5
IEC 62061
IEC 61511
SILCL
SIL
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3