Electrical Power Network Specification; Motor Connection Data; Control Unit Connection Data; Efficiency - ABB ACS880-07 Hardware Manual

Industrial drives (45 to 630 kw, 50 to 700 hp)
Hide thumbs Also See for ACS880-07:
Table of Contents

Advertisement

Electrical power network specification

Voltage (U
)
1
Network type
Short-circuit withstand
strength (IEC 61439-1)
Short-circuit current
protection (UL 508A)
Short-circuit current
protection
(CSA C22.2 No. 14-05)
Frequency
Imbalance
Fundamental power
factor (cos phi
)
1

Motor connection data

Motor types
Voltage (U
)
2
Frequency
Current
Switching frequency
Maximum recommended
motor cable length

Control unit connection data

Efficiency

Protection classes

Degrees of protection
(IEC/EN 60529)
Enclosure types (UL50)
ACS880-07-xxxxx-3 drives: 380...415 VAC 3-phase +10%...-15%
ACS880-07-xxxxx-5 drives: 380...500 VAC 3-phase +10%...-15%
ACS880-07-xxxxx-7 drives: 525...690 VAC 3-phase +10%...-15%
TN (grounded) and IT (ungrounded) systems
Maximum allowable prospective short-circuit current is 65 kA when the input
cable is protected with gG type fuses (IEC 60269) having maximum operating
time of 0.1 seconds and maximum current rating as follows:
• 400 A for frames R6 to R8
• 630 A for frame R9
• 1250 A for frames R10 and R11.
The drive is suitable for use on a circuit capable of delivering not more than
100,000 rms symmetrical amperes at 600 V maximum when the input cable is
protected with T class fuses.
The drive is suitable for use on a circuit capable of delivering not more than
100 kA rms symmetrical amperes at 600 V maximum when the input cable is
protected with T class fuses.
47 to 63 Hz, maximum rate of change 17%/s
Max. ± 3% of nominal phase to phase input voltage
0.98 (at nominal load)
Asynchronous AC induction motors, permanent magnet synchronous motors,
AC induction servomotors and ABB synchronous reluctance motors (SynRM
motors)
0 to U
, 3-phase symmetrical, U
1
0...500 Hz
See section
Ratings.
2.7 kHz (typically)
300 m (984 ft).
Note: With motor cables longer than 150 m (492 ft) the EMC Directive
requirements may not be fulfilled.
See chapter
Control unit of frames R6 to R9
of frames R10 and R11
Approximately 98% at nominal power level
IP22, IP42, IP54
UL Type 1, UL Type 1 Filtered, UL Type 12. For indoor use only.
at the field weakening point
max
on page
on page 129.
Technical data 191
119
or chapter
Control unit