90 Electrical installation
Note:
If there is a symmetrically constructed grounding conductor on the motor cable in addition to the conductive
shield, connect the grounding conductor to the grounding terminal at the drive and motor ends.
Do not use an asymmetrically constructed motor cable. Connecting its fourth conductor at the motor end
increases bearing currents and causes extra wear.
*) Switch-disconnector and separate fuses in frame R9
Layout of the power cable connection terminals and lead-throughs
(frames R6 to R8)
5
4
1
2
3
1
2
6
3
4
5
6
1
Strain relief
Power cable lead-throughs. Conductive sleeve
under the grommet. The grommets are
included in IP54 units only.
Control cable lead-through with EMI conductive
cushions.
PE terminal
Input power cable terminals L1, L2 and L3
Motor cable terminals U2, V2, W2