200 Technical data
Category C3
The drive complies with the standard with the following provisions:
1. The drive is equipped with EMC filter E200, E201 or E210.
2. The motor and control cables are selected as specified in the hardware manual.
3. The drive is installed according to the instructions given in the hardware manual.
4. Maximum motor cable length is 150 meters for frames R6 to R9 and 100 meters for
frames R10 and R11.
WARNING! A drive of category C3 is not intended to be used on a low-voltage public
network which supplies domestic premises. Radio frequency interference is expected if
the drive is used on such a network.
Category C4
If the provisions under
be met as follows:
1. It is ensured that no excessive emission is propagated to neighbouring low-voltage
networks. In some cases, the natural suppression in transformers and cables is
sufficient. If in doubt, the supply transformer with static screening between the primary
and secondary windings can be used.
Low
voltage
Equipment
2. An EMC plan for preventing disturbances is drawn up for the installation. A template is
available from the local ABB representative.
3. The motor and control cables are selected as specified in the hardware manual.
4. The drive is installed according to the instructions given in the hardware manual.
WARNING! A drive of category C4 is not intended to be used on a low-voltage public
network which supplies domestic premises. Radio frequency interference is expected if
the drive is used on such a network.
UL marking
cULus listed types: frames R6 to R9.
UL listing is pending for the other types.
Category C3
cannot be met, the requirements of the standard can
Medium voltage network
Neighbouring
network
Point of measurement
Equipment
(victim)
Supply transformer
Static screen
Low
voltage
Drive
Equipment