70 Guidelines for planning the electrical installation
Additional requirements for non-ABB high-output and IP23 motors
The rated output power of high output motors is higher than what is stated for the particular
frame size in EN 50347 (2001). The table below shows the requirements for random-
wound and form-wound non-ABB motors with nominal power smaller than 350 kW. For
bigger motors, consult the motor manufacturer.
Nominal AC line
voltage
Motor insulation
U
< 420 V
Standard: Û
N
1300 V
420 V < U
< 500 V Standard: Û
N
1300 V
or
Reinforced: Û
1600 V, 0.2
microsecond rise
time
500 V < U
< 600 V Reinforced: Û
N
1600 V
or
Reinforced: Û
1800 V
600 V < U
< 690 V Reinforced: Û
N
1800 V
Reinforced: Û
2000 V, 0.3
microsecond rise
time ***
*** If the intermediate DC circuit voltage of the drive is increased from the nominal level by resistor braking,
check with the motor manufacturer if additional output filters are needed in the applied drive operation
range.
ABB du/dt filter, insulated N-end bearing and ABB common
system
P
< 100 kW or frame
N
size < IEC 315
P
< 134 hp or frame
N
size < NEMA 500
=
+ N or CMF
LL
=
+ du/dt + (N or CMF)
LL
=
+ N or CMF
LL
=
+ du/dt + (N or CMF)
LL
=
+ N or CMF
LL
=
+ N + du/dt
LL
=
+ N + CMF
LL
Requirement for
mode filter
100 kW < P
IEC 315 < frame size < IEC 400
134 hp < P
NEMA 500 < frame size < NEMA 580
+ N + CMF
+ N + du/dt + CMF
+ N + CMF
+ N + du/dt + CMF
+ N + CMF
+ N + du/dt + CMF
+ N + CMF
< 350 kW or
N
< 469 hp or
N