Capacitors; Reforming The Capacitors - ABB ACS880-07 Hardware Manual

Industrial drives (45 to 630 kw, 50 to 700 hp)
Hide thumbs Also See for ACS880-07:
Table of Contents

Advertisement

172 Maintenance
R10 and R11
12
14
13

Capacitors

The drive intermediate circuit employs several electrolytic capacitors. Their lifespan
depends on the operating time of the drive, loading and ambient temperature. Capacitor
life can be prolonged by lowering the ambient temperature.
Capacitor failure is usually followed by damage to the unit and an input cable fuse failure,
or a fault trip. Contact ABB if capacitor failure is suspected. Replacements are available
from ABB. Do not use other than ABB specified spare parts.

Reforming the capacitors

The capacitors must be reformed if the drive has been stored for a year or more. See page
48
for information on finding out the manufacturing date. For information on reforming the
capacitors, see Converter module capacitor reforming instructions (3BFE64059629
[English]).

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents