184 Technical data
Drive type
ACS880-07-0425A-7
ACS880-07-0470A-7
ACS880-07-0522A-7
ACS880-07-0590A-7
ACS880-07-0650A-7

Terminal and lead-through data for the power cables

IEC

Frame
Number of holes
size
in the lead-
through plate for
the power cables.
Hole diameter
60 mm.
R6
6
R7
6
R8
6
R9
9
R10
12
R11
12
US
Frame
Terminals L1, L2, L3, U2, V2, W2, UDC+/R+, UDC- and R-
size
Max. phase
conductor size
AWG/kcmil
R6
350 MCM
R7
R8
1×500 MCM or
2×350 MCM
R9
2×500 MCM
R10
1×500 MCM or
4×350 MCM
R11
1×500 MCM or
4×350 MCM
Frame
3
m
/h
R11
2950
R11
2950
R11
2950
R11
2950
R11
3170
Terminals L1, L2, L3, U2, V2, W2, UDC+/R+,
Max. phase
conductor
size
2
mm
185
185
1×240 or
2×185
3×240
3×240 or
4×185
3×240 or
4×185
Busbar bolt
size – Hole
spacing
M10 (3/8") × 2
– 1.75"
M12 (7/16") × 2
– 1.75"
M12 (7/16") × 4
– 1.75"
Air flow
Heat dissipation
3
ft
/min
1837
1837
1837
1837
1978
UDC- and R-
Bolt size
Tightening
torque
M10
20...40 N·m
M12
50...75 N·m
Tightening torque
bf·ft
15...30
37...55
Noise
W
dB(A)
6909
8622
9264
10362
11078
Grounding terminals
Bolt size
Tightening
M10
30...44 N·m
Grounding terminals
Bolt size
Tightening torque
bf·ft
M10 (3/8")
22...32
72
72
72
71
71
torque
N·m