6.3 Setting up an auxiliary heat source for space heating

EPRA14~18D + ETVH16SU18+23E
Daikin Altherma 3 H HT F
4P644738-1D – 2023.10
Efficiency.
-
Depending on the demand, the indoor unit supplies different leaving water
temperature matching the design temperature of the different heat emitters.
-
Underfloor heating has the best performance with the heat pump system.
INFORMATION
Bivalent is only possible in case of 1 leaving water temperature zone with:
room thermostat control, OR
external room thermostat control.
Space heating can be done by:
-
The indoor unit
-
An auxiliary boiler (field supply) connected to the system
When there is a heating request, the indoor unit or the auxiliary boiler starts
operating. Which of these units operates, depends on the outdoor temperature
(status of the changeover to external heat source). When the permission is given
to the auxiliary boiler, the space heating by the indoor unit is turned OFF.
Domestic hot water is always produced by the DHW tank connected to the
indoor unit.
Bivalent operation is only possible if space heating is turned ON.
INFORMATION
During heating operation of the heat pump, the heat pump operates to achieve
the desired temperature set via the user interface. When weather-dependent
operation is active, the water temperature is determined automatically
depending on the outdoor temperature.
During heating operation of the auxiliary boiler, the auxiliary boiler operates to
achieve the desired water temperature set via the auxiliary boiler controller.
Setup
Integrate the auxiliary boiler as follows:
A Main leaving water temperature zone
B One single room
6
Application guidelines
|
B
b
b
c
d
c
A
e
a
Installer reference guide
49