12.4: Installation

The Nexus® Switchboard Meter provides two-step installation or disconnection.
1. Insert the case into a prepared mounting hole for the switchboard case. Secure with mounting
screws. Before installing the meter, check the battery connections (sections 6.2, 5.4.4).
2. Slide the meter into the case and secure by sliding the chassis levers until they snap into place.
Connectors for the following are located on the back of the meter. The connectors will
automatically plug into the available connectors on the mounting board (see figure below).
Pulse Outputs - Four Channels
Status Inputs
Phone
Line/Network
Power In
COM4, COM1
IRIG-B
Modem Gateway RS485
Position the case front against the four screw holes. Secure the front of the case by turning the four
built-in screws in each of the corners.
Built-in
Screws
Electro Industries/GaugeTech
Fig. 12.7: Front Case showing Built-In Screws
Doc # E151701
12-6