The Modbus Map for the Analog Output Module (and operating details) can be found in the Modbus
Communicating Output Modules Manual.

10.5.2: Normal Mode

Normal Mode is the same for the 0-1mA and the 4-20mA Analog Output Modules except for the
number of processes performed by the modules.
Both devices:
1. Accept new values through communication.
2. Output current loops scaled from previously accepted values.
The 0-1mA module includes one more process in its Normal Mode:
3. Read and average the A/D and adjust values for Process 2 above.
.
The device will operate with the following default parameters:
Address
Baud Rate
Transmit Delay Time
Normal Operation is prevented by a number of occurrences. See Section 10.4.1 for details.
Electro Industries/GaugeTech
247 (F7H)
57600 Baud
0