Limit & Waveform Full Scales
These settings are based on a percentage of Full
Scales, which are derived from the CT Ratios and
can be changed without effecting accuracy. Be
sure to set the CT Ratios first.
Time Settings
(not shown)
(Initial Setting is - 5:00 Eastern Time)
- 6:00 = Central Time
- 9:00 Pacific Time
- 7:00 = Mountain Time
-10:00 Hawaii
- 8:00 = Pacific Time
-11:00 Midway Island
Daylight Savings Time: choose from Disabled; Auto DST to
enable pre-2007 Daylight Savings Time; User Defined, and
Auto DST U.S. EPA 2005 to enable the standard U.S. DST schedule.
Line Synchronization: Enable/Disable and choose Frequency.
Communications Settings
Ports 1 & 4 are programmable. Port 4 is INITIALLY
SET for External Devices and can be changed. For
Internal Modem & Network Options, set Advanced
Settings & Dial Out Profile.
Revenue & Energy Settings
Block Average Demand
Input settings for Demand Integration. Click OK.
Display Configuration - Screen Assignments
Use pull down windows to set up Display Modes & Screens.
Power Quality & Alarm Settings
Limits
Double-click on a column or setting, change setting. Click OK.
Waveform - CBEMA Profile (PQ Thresholds)
Triggers for waveforms are set here based on a percentage of Full
Scales (set on the Limit & Waveform Full Scales screen).
Set Sampling Rate and Total Captures. Click OK.
Trending Profile Settings
Log Time Intervals (not shown)
Set Intervals for Time Stamps from 1 second to 18 Hours. Based on
Nexus time. Click OK. Time is set in the Tools Menu.
Trending Setup for Historical Logs (not shown)
Using pull down menus, select Type of Snapshot and Channel.
Click Add or Remove. A running Total of Bytes Used appears on
the screen. Click OK.
NOTE: This guide is intended to be a brief tutorial for the Installation
®
and Configuration of the Nexus
does not purport to cover all details or variations in equipment. All
work should be done by appropriate qualified personnel. For details,
refer to later chapters & Communicator EXT User Manual.
Electro Industries/Gauge Tech
1262/1272 Power Meter. This guide
Doc # E151701
Q-2