Sense Input Voltage
•
Rated 0 to 332 Volts line-to-neutral; 0 to 480 Volts line-to-line.
•
Operating 96 to 332 Volts line-to-neutral; 155 to 576 Volts line-to-line.
Input Voltage - Self-Powered Option Power Supply
•
Rated 96 to 332 Volts line-to-neutral; 155 to 576 Volts line-to-line.
Input Voltage - Low Voltage Power Supply
•
Rated 30 to 90 Volts line-to-neutral; 52 to 155 Volts line-to-line.
Input Current
•
Transformer Rated Continuous 120% of meter class.
•
Defined as Class 20 (Class 2 and Class 10 Available).
•
Nominal current rating: 5A for Class 20 and 10 meters; 1A for Class 2 meters.
•
Overload 500% for 1 second, non-recurring.
•
Three or four current inputs depending on form (I
Frequency
•
45-62 Hz.
Burden (Sense Inputs)
•
Voltage Inputs: 0.33VA@576V.
•
Current Inputs: 0.0125VA@25A.
Isolation
•
All inputs and outputs isolated to 2500 Volts.
•
Com Ports isolated from each other to 1000 Volts.
Sensing
•
Accu-Measure
TM
•
2x16-bit A/D converter (1272). 1x16-bit A/D Converter (1262).
•
True RMS.
•
8-Channel Sample and Hold.
Memory
•
All meter setup parameters, measurements and logs contained in nonvolatile RAM.
Compliance
•
ANSI C12.20 Class 0.2 and IEC60687 (Accuracy).
•
ANSI C37.90.1 (Surge Withstand).
•
ANSI C62.41 (Surge Immunity).
•
ANSI C12.18 (Optical Port).
•
IEC 61000-4-15 (Flicker) (1272).
Standard Communications
•
LCD Display.
•
ANSI Type 2 Optical Port (IR Port).
•
Two RS485 Serial Ports.
•
Modbus RTU, Modbus ASCII and DNP 3.0 protocols.
•
Data Speeds of up to 115k bps.
Optional Communications
•
INP2: Internal Modem with data buffering for faster downloads and noise rejection.Connect
speeds of 300 to 56k bps.
•
INP200: Internal 10Mbit Ethernet.
•
INP202: Ethernet (INP200) / Modem (INP2) Combination
Electro Industries/GaugeTech
Technology.
Doc # E151701
, I
, I
and I
).
A
B
C
N