Nexus® Meter's Time-o o f-U U se Function

7.1: Introduction

A Time-of-Use (TOU) usage structure takes into account the quantity of energy used and the time at
which it was consumed. The Nexus® 1262/1272 meter's TOU function, available with the
Communicator EXT software, is designed to accommodate a variety of programmable rate struc-
tures. The TOU function accumulates data based on the time-scheme programmed into the Nexus®
meter.
See the Communicator EXT User Manual for details on programming the Nexus® 1262/1272
meter's TOU calendar and retrieving TOU data.
7.2: The Nexus® Meter's TOU Calendar
A Nexus® meter's TOU calendar sets the parameters for TOU data accumulation. You may store up
to twenty calendars in the Nexus® meter and an unlimited amount of calendar files on your
computer.
The TOU calendar profile allows you to assign a programmable usage schedule—eg, "Weekday,"
"Weekend," "Holiday"—to each day of the calendar year. You may create up to 16 different TOU
schedules.
Each TOU schedule divides the 24-hour day into fifteen-minute intervals from 00:00:00 to 23:59:59.
You may apply one of eight different programmable registers—eg "Peak," "Off Peak," "Shoulder
Peak"— to each fifteen-minute interval.
The Nexus® meter stores:
accumulations on a seasonal basis, up to four seasons per year;
accumulations on a monthly basis.
Seasonal and monthly accumulations may span one year into the next. Each season and month is
defined by a programmable start/billing date, which is also the end-date of the prior season or month.
A season ends at midnight of the day before the start of the next season.
A month ends at midnight of the month's billing day.
If the year ends and there is no new calendar, TOU accumulations will stop. If a calendar is present
for the following year, TOU accumulations continue until the next monthly bill date or next
start-of-season is reached. Accumulation can span into the following year.
If no following year is present, the last accumulation for the year will end on 12:31:23:59:59.