4: Exiting Test Mode - Electro Industries Nexus 1262 Installation & Operation Manual

Billing meters
Table of Contents

Advertisement

Settings can be preset for the following sets
of values:
Primary Energy, Secondary Energy, Primary
Energy (Quadrants), Secondary Energy
(Quadrants), Internal Input Accumulators,
KYZ Output Accumulators, Q Hours, I & V
Squared T Accumulators, Cumulative Demand
(Secondary) and Uncompensated Energy.
Examples of some of the screens are shown here.
1. Click the Preset Boxes for the values you want to set.
2. Click Set to save your entries or Cancel to exit the
screen without saving any changes.

4.2.4: Exiting Test Mode

Exit Test Mode in one of the following three ways:
1. Pressing and holding the Test Button for more than 3 seconds.
2. By the Test Mode Time-Out Timer, if no load is present.
3. By the Extended Test Mode Time-Out Timer, if load is present.
These options are explained further in the following sections.
Pressing the Test Mode Button for more than three seconds ends Test Mode and returns the meter
to Normal Mode.
The Test Mode Time-Out Timer has two modes of operation, depending on whether the meter sees
measurable load.
If the meter does not recognize measureable load:
The meter watches for user interaction by monitoring activity on the Test Button and the Reset
Button. If neither button is pushed within the programmed Exit Delay time, the meter
e
Doc # E151701
4-6
Electro Industries/GaugeTech