Overview; Figure 9.1: Nexus P40N Led External Display - Electro Industries Nexus 1262 Installation & Operation Manual

Billing meters
Table of Contents

Advertisement

Using the Nexus

9.1: Overview

The Nexus® 1262/1272 Socket Meters have a backlit LCD display built into the meter. In addition,
Electro Industries offers two optional external displays, each powered by an additional power supply
(such as PSIO). The P40N is our LED display, which provides easy-to-use access to the information
stored in the Nexus® meter. The P60N is our Touch Screen Display, which provides easy access to
Nexus® meter readings and information combined with a graphical touch screen presentation.
Plug one of the Nexus® External Displays into the Port 1 or Port 4 wiring connection using the
RS485 cable supplied (see Figure 6.11 for wiring details). The Displays operate at 9600 baud. To use
the Displays on another port, configure that port to operate at 9600 baud, using the Communicator
EXT Software; see the Communicator EXT User Manual.
9.2: Nexus
P40N LED External Display
®
The Nexus® P40N LED External Display has three modes:
Dynamic Readings Mode (sections 9.3 and 9.4)
Nexus® Information Mode (sections 9.5 and 9.6)
Display Features Mode (sections 9.7 and 9.8)
Each Mode is divided into Groups. Most Groups are further broken down into Readings.
Use the MODE button to scroll between Modes.
Use the UP/DOWN arrows to scroll from Group to Group within each Mode.
Use the LEFT/RIGHT arrows to scroll from Reading to Reading within each Group.
Use Communicator EXT software to Flash Update the P40N External Display. VA Rating is 5.
LED Display
Up/Down Arrows
e
Electro Industries/GaugeTech
Chapter 9
External Displays
®
®
Figure 9.1: Nexus
P40N LED External Display
Doc # E151701
Left/Right Arrows
Mode Button
9-1