5.3.14: Programming Modems for Remote Communication

When a modem speaks to most RS485 or RS232-based devices, it must be programmed to certain
settings for the communication to work. This task is often quite complicated. Modem Manager was
designed to eliminate this step.
If you are not using a Modem Manager device, you must follow the steps below to communicate with
the remote meter(s). Consult your modem's manual for the proper string settings or see Section 5.3.16
for a list of selected modem strings.
Modem Connected to a Computer (the Originate Modem):
Restore modem to factory settings. This erases all previously programmed settings.
Set modem to display Result Codes. The computer will use the result codes.
Set modem to Verbal Result Codes. The computer will use the verbal result codes.
Set modem to use DTR Signal. This is necessary for the computer to ensure connection with the
originate modem.
Set modem to enable Flow Control. This is necessary to communicate with remote modem
connected to the Meter.
Tell modem to write the new settings to activate profile. This places these settings into
nonvolatile memory; the setting will take effect after the modem powers up.
Modem Connected to the meter (the Remote Modem):
Restore modem to factory settings. This erases all previously programmed settings.
Set modem to auto answer on n rings. This sets the remote modem to answer the call after n
rings.
Set modem to ignore DTR Signal. This is necessary for the Meter to ensure connection with
originate modem.
Set modem to disable Flow Control. RS232 communication does not support this feature.
Tell modem to write the new settings to activate profile. This places these settings into
nonvolatile memory; the setting will take effect after the modem powers up.
When programming the remote modem with a terminal program, make sure the baud rate of the
terminal program matches the meter's baud rate.
e
Electro Industries/Gauge Tech
Doc # E151701
5-16