Inp202 Ethernet/Modem Combination; 1: Hardware Overview - Electro Industries Nexus 1262 Installation & Operation Manual

Billing meters
Table of Contents

Advertisement

After the Network parameters are set, Communicator EXT will connect to the meter via the
Network using a Device Address of "1" and the assigned IP Address. Follow these steps:
1. Double click on the Communicator EXT icon to open the software.
2. Click the Connect icon in the icon tool bar. You will see the Connect screen.
3. Click the Network button at the top of the screen. The screen will change to one requesting the
following information:
Device Address:
Host:
Network Port:
Protocol:
4. Click the Connect button at the bottom of the screen. Communicator EXT connects to the
meter via the Network.
NOTE: Communicator EXT always communicates Modbus TCP which is the default protocol
for Nexus® meters.
NOTE: Nexus® meters do not support web pages, email, FTP, or DHCP communication.

5.6: INP202 Ethernet/Modem Combination

The INP202 Option is an extension of INP200. It has all the features of INP200 plus a built-in
modem. The communication protocol supported by the modem is Modbus ASCII. The
communication protocol supported by the RS485 Ethernet/Modem Gateway is Modbus RTU.
INP202 converts all incoming Modem Modbus ASCII requests to Modbus RTU for internal and
gateway communication. It then converts all response Modbus RTU messages into Modbus ASCII
and sends the responses to the modem.

5.6.1: Hardware Overview

The Nexus® 1262/1272 meter with the INP202 Option has all the components of an INP200
Nexus® meter plus a built-in modem. It has the capability of connecting to a network through an
Ethernet LAN and with other devices via modem.
e
Electro Industries/GaugeTech
1
IP Address (per your network administrator).
Example: 10.0.0.1
502
Modbus TCP
Doc # E151701
5-23

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nexus 1271

Table of Contents