Internal 8-Channel Digital KYZ Pulse/Status Inputs
Type: Self-excited, for dry contacts only.
Wetting Voltage: 12V dc typical.
Internal 4-Channel KYZ Outputs
Type: Form C.
On Resistance: 23-35Ω.
Peak Voltage: 350V dc.
Continuous Load Current: 120mA.
Peak Load Current: 350mA (10ms).
Off-State Leakage Current @350V dc : 1 µA.
Opto Isolation: 3750Vrms (60 Hz, 1 min.).
Timing
IRIG-B input for synchronizing to external GPS clock signal.
Line Frequency Synchronization.
Internal Clock.
Environmental
Operating Temperature: (-40 to +85)°C.
Display Operating Temperature: (-20 to +70)°C.
Humidity: 95% non-condensing.
Storage Temperature: (-40 to +85)°C.
Lexan Cover.
Power Supply (Unit is powered by 3-Phase Voltage Sense Inputs.)
(96 to 550)V ac 50/60Hz (576V ac absolute maximum), Autoranging 3-Phase Power Supply.
Meter power requirement 3VA/Phase @ 120V ac worst case.
Meter power provided by any of the 3-Phase voltage sources being monitored.
Aux Power Supply Option (Unit is powered by Aux Pigtail Wire.)
Select Power Supply Option "SE" in ordering information.
Input Voltage: 102 to 270V AC/DC 50/60Hz
Maximum Power Consumption: 12VA@276V ac .
Security
Hardware lock secures meter settings.
Two 10-character passwords.
One password controls access to read meter digitally.
Separate password controls access to program meter.
Internal Battery
Panasonic BR2032 3V Lithium Battery (or equivalent) maintains NVRAM and time during
outages.
Modem Battery
3V Lithium Battery with custom leads and velcro mounting maintains Dial-Back Feature during
outages. Call factory for replacement battery.