Connections
Connect the Switching Hub and PLC using an FQ-WN@@ Special Ethernet Cable.
Setup Tool
Touch Finder or PC Tool
Standard RJ45
Ethernet Cable
Important
When connecting more than one Sensor, set the IP addresses so that the same IP address is not used for
more than one Sensor.
Set the Basic Settings of the Ethernet
Use the following procedure to turn OFF automatic settings for Ethernet, and enter the IP address and subnet
mask.
[Sensor settings]  [Network]  [Ethernet]
1
Press [Auto connection].
2
Press [OFF] to select it.
You can now set the IP address manually.
3
Enter the IP address and subnet mask.
Item
IP address
Subnet mask
Note
The port number is always 9876.
130
Outputting/Controlling with Ethernet
PLC to control Sensor
Switching Hub
Standard RJ45
Ethernet Cable
Special
Ethernet Cable
Purpose
Enter the IP address of the Sensor.
Enter the subnet mask.
FQ Sensor
Setting range
a.b.c.d
a:1 to 223
b: 0 to 255
c: 0 to 255
d: 2 to 254
(Default: 10.5.5.100)
0.0.0.0 to 255.255.255.255
(Default: 255.255.255.0)
FQ User's Manual