Delta AH500 series Hardware Manual page 228

Programmable logic controllers
Hide thumbs Also See for AH500 series:
Table of Contents

Advertisement

Error
Description
code
The bus of AH10DNET-5A
16#A0F4
becomes OFF.
AH10DNET-5A detects that
16#A0F5
there is no network power
supply to the DeviceNet.
Something is wrong with the
16#A0F6
internal memory of
AH10DNET-5A.
Something is wrong with the
16#A0F7
data exchange unit of
AH10DNET-5A.
The product ID of
16#A0F8
AH10DNET-5A is incorrect.
An error occurs when the
data is read from
16#A0F9
AH10DNET-5A, or when the
data is written into
AH10DNET-5A.
The node ID of
AH10DNET-5A is the same
16#A0FA
as that of the slave set in the
scan list.
C h ap te r 9 Tro ub les ho o ti ng
Remedy
1. Check whether the communication cable is
normal, and whether the shielded cable is
grounded.
2. Check whether the serial transmission speeds of
other devices on the network are the same.
3. Check whether the both ends of the cable are
connected to 121 Ω terminal resistors.
4. Supply power to AH10DNET-5A again.
Check whether the communication cable is normal,
and whether the network power supply is normal.
Supply power to AH10DNET-5A again. If the error still
occurs, please contact the factory.
Supply power to AH10DNET-5A again. If the error still
occurs, please contact the factory.
Supply power to AH10DNET-5A again. If the error still
occurs, please contact the factory.
Supply power to AH10DNET-5A again. If the error still
occurs, please contact the factory.
1. Set the node ID of AH10DNET-5A again. The new
node ID can not be the same as the node ID of the
slave set in the scan list. Supply power to
AH10DNET-5A again.
2. Put no slave in the scan list, and download the
blank scan list to AH10DNET-5A through the
simulated online mode in the software. Supply
power to AH10DNET-5A again.
9 - 3 3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents