Error
Description
code
The module ID or the setting
16#630A
of the module is different from
the setting in the Ether Link.
The setting of the netmask
address for the CPU or the
16#630B
module is different from the
setting in the Ether Link.
The node number exceeds
16#6602
the limit. (SM1598)
The device is undefined.
16#6603
(SM1599)
The CPU parameter
downloaded is incorrect.
16#8230
The IP address is illegal.
The CPU parameter
downloaded is incorrect.
16#8231
The netmask address is
illegal.
The CPU parameter
downloaded is incorrect.
16#8232
The gateway address is
illegal.
The CPU parameter
downloaded is incorrect.
16#8233
The IP address filter is set
incorrectly.
The CPU parameter
downloaded is incorrect.
16#8235
The static ARP table is set
incorrectly.
The CPU parameter
downloaded is incorrect.
16#8237
The network number is illegal.
The CPU parameter
downloaded is incorrect.
16#8238
The node number is illegal.
The CPU parameter
downloaded is incorrect.
16#8239
The email is set incorrectly.
The CPU parameter
downloaded is incorrect.
16#823A
The trigger in the email is set
incorrectly.
The CPU parameter
downloaded is incorrect.
16#823B
The TCP socket is set
incorrectly.
C h ap te r 9 Tro ub les ho o ti ng
Remedy
1. Check the setting of the parameter in
HWCONFIG.
2. Check the setting of the Ether Link in
NWCONFIG.
1. Check the setting of the parameter in
HWCONFIG.
2. Check the setting of the Ether Link in
NWCONFIG.
Check the network configuration in NWCONFIG,
and download it again.
Check the network configuration in NWCONFIG,
and download it again.
1. Check the Ethernet parameter in the CPU
module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
1. Check the Ethernet parameter in the CPU
module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
1. Check the Ethernet parameter in the CPU
module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
1. Check the Ethernet parameter in the CPU
module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
1. Check the Ethernet parameter in the CPU
module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
1. Check the network configuration in NWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
1. Check the network configuration in NWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
1. Check the Ethernet parameter in the CPU
module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
1. Check the Ethernet parameter in the CPU
module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
1. Check the Ethernet parameter in the CPU
module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.