Delta AH500 series Hardware Manual page 222

Programmable logic controllers
Hide thumbs Also See for AH500 series:
Table of Contents

Advertisement

Error
Description
code
The comparison value for
16#A004
channel 1 exceeds the range.
The limit value of the alarm
16#A005
output for channel 1 is
incorrect.
The interrupt number for
16#A006
channel 1 exceeds the range.
The linear accumulation in
16#A011
channel 2 exceeds the range.
The prescale value for
16#A012
channel 2 exceeds the range.
The moving average for
16#A013
channel 2 exceeds the range.
The comparison value for
16#A014
channel 2 exceeds the range.
The limit value of the alarm
16#A015
output for channel 2 is
incorrect.
The interrupt number for
16#A016
channel 2 exceeds the range.
The linear accumulation in
16#A021
channel 3 exceeds the range.
The prescale value for
16#A022
channel 3 exceeds the range.
The moving average for
16#A023
channel 3 exceeds the range.
The comparison value for
16#A024
channel 3 exceeds the range.
The limit value of the alarm
16#A025
output for channel 3 is
incorrect.
The interrupt number for
16#A026
channel 3 exceeds the range.
The linear accumulation in
16#A031
channel 4 exceeds the range.
C h ap te r 9 Tro ub les ho o ti ng
Remedy
Check the module parameter in HWCONFIG.
The comparison value for channel 1 should be
within the range between -999999999 and
999999999.
Check the module parameter in HWCONFIG.
The limit value of the alarm output for channel 1
should be within the range between -200000 and
200000.
Check the module parameter in HWCONFIG.
The interrupt number for channel 1 should be within
the range between 0 and 31.
To clear the linear accumulation, users need to set
bit 1 in CR28 to ON by means of FROM/TO.
Check the module parameter in HWCONFIG.
The prescale value for channel 2 should be within
the range between 0 and 32767.
Check the module parameter in HWCONFIG.
The moving average for channel 2 should be within
the range between 2 and 60.
Check the module parameter in HWCONFIG.
The comparison value for channel 2 should be
within the range between -999999999 and
999999999.
Check the module parameter in HWCONFIG.
The limit value of the alarm output for channel 2
should be within the range between -200000 and
200000.
Check the module parameter in HWCONFIG.
The interrupt number for channel 2 should be within
the range between 0 and 31.
To clear the linear accumulation, users need to set
bit 1 in CR56 to ON by means of FROM/TO.
Check the module parameter in HWCONFIG.
The prescale value for channel 3 should be within
the range between 0 and 32767.
Check the module parameter in HWCONFIG.
The moving average for channel 3 should be within
the range between 2 and 60.
Check the module parameter in HWCONFIG.
The comparison value for channel 3 should be
within the range between -999999999 and
999999999.
Check the module parameter in HWCONFIG.
The limit value of the alarm output for channel 3
should be within the range between -200000 and
200000.
Check the module parameter in HWCONFIG.
The interrupt number for channel 3 should be within
the range between 0 and 31.
To clear the linear accumulation, users need to set
bit 1 in CR84 to ON by means of FROM/TO.
9 - 2 7