Delta AH500 series Hardware Manual page 199

Programmable logic controllers
Hide thumbs Also See for AH500 series:
Table of Contents

Advertisement

AH5 00 Hardw are Manu al
Error
Description
code
16#0019
The USB is abnormal. (SM9)
The communication setting of
16#0033
COM1 is incorrect. (SM9)
The setting of the station
16#0034
address of COM1 is incorrect.
(SM9)
The setting of the
16#0035
communication type of COM1
is incorrect. (SM9)
The interval of retrying the
sending of the command
16#0036
through COM1 is set
incorrectly.(SM9)
The number of times the
sending of the command
16#0037
through COM1 is retried is set
incorrectly. (SM9)
The communication setting of
16#0038
COM2 is incorrect. (SM9)
The setting of the station
16#0039
address of COM2 is incorrect.
(SM9)
The setting of the
16#003A
communication type of COM2
is incorrect. (SM9)
The interval of retrying the
sending of the command
16#003B
through COM2 is set
incorrectly.(SM9)
The number of times the
sending of the command
16#003C
through COM2 is retried is set
incorrectly. (SM9)
The memory card is initialized
16#005E
incorrectly. (SM453)
The data is read from the
inexistent file in the memory
16#005F
card, or the data is written into
the inexistent file in the
memory card. (SM453)
The default folder can not be
16#0060
created in the CPU module.
(SM453)
9 - 4
Remedy
Retry the connection. If the error still occurs, please
contact the factory.
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the
CPU module in HWCONFIG again.
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the
CPU module in HWCONFIG again.
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the
CPU module in HWCONFIG again.
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the
CPU module in HWCONFIG again.
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the
CPU module in HWCONFIG again.
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the
CPU module in HWCONFIG again.
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the
CPU module in HWCONFIG again.
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the
CPU module in HWCONFIG again.
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the
CPU module in HWCONFIG again.
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the
CPU module in HWCONFIG again.
Check whether the memory card breaks down.
Check whether the file path is correct.
Check whether the capacity of the memory card is
large enough, or whether the memory card breaks
down.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents