Error
Description
code
There is a routing response
16#6606
timeout.
The contents of the program
downloaded are incorrect.
16#8105
The program syntax is
incorrect.
The contents of the program
downloaded are incorrect.
16#8106
The length of the execution
code exceeds the limit.
The contents of the program
downloaded are incorrect.
16#8107
The length of the source code
exceeds the limit.
The communication port
parameter downloaded is
incorrect.
16#820E
The communication protocol is
incorrect.
The communication port
parameter downloaded is
incorrect.
16#820F
The setting of the station
address is incorrect.
The communication port
parameter downloaded is
incorrect.
16#8210
The choice among RS-232,
RS-485, and SR-422 is
incorrect.
The communication port
parameter downloaded is
incorrect.
16#8211
The interval of retrying the
sending of the command is set
incorrectly.
The communication port
parameter downloaded is
incorrect.
16#8212
The number of times the
sending of the command is
retried is set incorrectly.
The CPU parameter
downloaded is incorrect.
16#8215
The interval of executing
interrupt 0 is set incorrectly.
C h ap te r 9 Tro ub les ho o ti ng
Remedy
1. Check the network configuration in NWCONFIG.
2. Check whether the setting of the communication
timeout conform to the practical application.
1. Check whether the program syntax which is not
supported by the CPU module is used, and
check whether the version of the firmware has
its special limitation.
2. Check whether the version of ISPSoft used to
create the program is the same as the version of
ISPSoft used now.
1. Shorten the length of the program, and
download the program again.
2. Check whether the version of ISPSoft used to
create the program is the same as the version of
ISPSoft used now.
1. Shorten the length of the program, and
download the program again.
2. Check whether the version of ISPSoft used to
create the program is the same as the version of
ISPSoft used now.
1. Check the setting of the communication port
parameter for the CPU module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
1. Check the setting of the communication port
parameter for the CPU module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
1. Check the setting of the communication port
parameter for the CPU module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
1. Check the setting of the communication port
parameter for the CPU module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
1. Check the setting of the communication port
parameter for the CPU module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
1. Check the setting of the basic parameter for the
CPU module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.