Delta AH500 series Hardware Manual page 207

Programmable logic controllers
Hide thumbs Also See for AH500 series:
Table of Contents

Advertisement

AH5 00 Hardw are Manu al
Error
Description
code
UDP connection failure
16#600B
(SM1091)
The TCP socket has been
16#600C
used. (SM1109)
The RJ45 port is not
16#600D
connected.
The email connection is busy.
16#6100
(SM1113)
The attachment in the email
16#6104
does not exist. (SM1113)
The attachment in the email is
16#6105
oversized. (SM1113)
There is an SMTP server
16#6107
response timeout. (SM1113)
The local communication port
16#6201
set in the TCP socket function
is illegal.
The remote communication
16#6202
port set in the TCP socket
function is illegal.
The device from which the data
16#6203
is sent in the TCP socket
function is illegal.
The transmitted data length set
16#6204
in the TCP socket function is
illegal.
The data which is sent through
16#6205
the TCP socket exceeds the
device range.
9 - 1 2
Remedy
1. Check the actual network configuration, and
check whether the number of UDP connections
exceeds the upper limit supported by the CPU
module.
2. Retry the TCP connection later. (This error does
not cause the PLC to stop running. Users can
perform the corresponding remedy by means of
the related flag in the program.)
1. Check whether the actual data access results in
the use of the same socket.
2. Change the socket number, or retry the socket
later. (This error does not cause the PLC to stop
running. Users can perform the corresponding
remedy by means of the related flag in the
program.)
Check the communication cable.
Retry the email connection later. (This error does
not cause the PLC to stop running. Users can
perform the corresponding remedy by means of
the related flag in the program.)
Check whether the attachment exists in the
memory card.
Check the size of the file which is specified as the
attachment. If the size is over 2 MB, the file can
not be specified as the attachment.
1. Check whether the status of the SMTP server is
normal.
2. Retry the sending of the email later. (This error
does not cause the PLC to stop running. Users
can perform the corresponding remedy by
means of the related flag in the program.)
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG again.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG again.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG again.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG again.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG again.