Avaya DEFINITY Server CSI Maintenance Manual page 1915

Table of Contents

Advertisement

XXX-BD (Common Port Circuit Pack)
If the circuit pack is not in the system, insert a circuit pack (in the same slot
as the error indicates) to resolve this error. Or, if the circuit pack is in the
system and the red LED is on, follow the instructions for "Red (alarm)" in
the
''Circuit Packs''
b. This error indicates the circuit pack has been busied out. Release the
circuit pack via release board PCSS.
c. The circuit pack has been logically administered but not physically
installed. The alarm should clear when the circuit pact is installed.
If the circuit pack is already installed:
1. Run test board PCSS long and look at any test failures or error
2. If the test does not clear error 23, then execute reset board PCSS
3. If the reset/test does not clear error 23, replace the circuit pack.
d. A wrong circuit pack is inserted in the slot where this circuit pack is logically
administered. To resolve this problem, either remove the wrong circuit pack
and insert the logically administered circuit pack OR use the change
circuit-pack command to readminister this slot to match the circuit pack
inserted.
e. This error indicates transient communication problems with this circuit
pack. This error is not service-affecting and no action is required.
f. This error, when reported with Aux data in the range of 4352 to 4358,
indicates that the circuit pack has reported an on-board hardware failure.
The circuit pack continuously tests the hardware and report the results
approximately every 10 minutes. If the hardware problem is resolved, the
"leaky bucket" strategy should clear the alarm in approximately 30 minutes.
However, if the alarm does NOT clear in 30 minutes, the circuit pack should
be replaced.
g. This error can be ignored, but look for other errors on this circuit pack.
h. This error is not service-affecting and no action is required.
i. This error indicates that no ringing current is detected. Run Test #51,
Ringing Application Test, and follow the procedures for Test #51. This error
is only applicable to Analog Line circuit packs.
j. The hyperactive circuit pack is out-of-service and may exhibit one or more
of the following symptoms:
1. The common circuit pack level tests such as Test #51 and/or Test
2. The tests run on the ports of this circuit pack are returning with a
3. A busyout/release of the circuit pack has no affect on test results.
4. A list configuration command shows that the circuit pack and ports
555-233-119
section in
codes generated.
and run the long test again.
#220 are aborting with error code 2000.
NO-BOARD.
are properly installed.
Chapter 1, ''Maintenance for CSI systems''
Issue 5 October 2002
1915