11 MANUAL CONTROL

11.2.5 JOG operation example

PLC READY signal
QD75 READY signal
Forward run JOG start signal
[Y8, YA, YC, YE]
Axis stop signal
[Y4, Y5, Y6, Y7]
BUSY signal[XC, XD, XE, XF] OFF
Fig. 11.7 Operation when the stop signal is turned ON during JOG operation
When the "stop signal" is turned ON during JOG operation
When the "stop signal" is turned ON during JOG operation, the JOG operation will
stop by the "deceleration stop" method.
JOG start signals will be ignored while the stop signal is ON.
The operation can be started by turning the stop signal OFF, and turning the JOG
start signal from OFF to ON again.
ON
[Y0]
OFF
ON
[X0]
OFF
ON
OFF
OFF
ON
POINT
The QD75 will not receive a "JOG start signal" while the "stop signal" is ON.
ON
11 - 13
MELSEC-Q
A JOG start signal OFF
ON
while the stop signal is ON will be ignored.