5 DATA USED FOR POSITIONING CONTROL
Setting value
0 : End
1 : Continue
Setting value
00
: Block start
H
(Normal start)
01
: Condition start
H
02
: Wait start
H
03
: Simultaneous
H
start
04
: Repeated start
H
(FOR loop)
05
: Repeated start
H
(FOR condition)
06
: NEXT start
H
Da.11 Shape
Set whether to carry out only the local "block start data" and then end control, or to
execute the "block start data" set in the next point.
Execute the designated point's "block start data", and then complete the control.
Execute the designated point's "block start data", and after completing control, execute the next
point's "block start data".
Da.12 Start data No.
Set the "positioning data No." designated with the "block start data".
Da.13 Special start instruction
Set the "special start instruction " for using "high-level positioning control". (Set
how to start the positioning data set in "
Execute the random block positioning data in the set order with one start.
Carry out the condition judgment set in "condition data" for the designated positioning data, and
when the conditions are established, execute the "block start data". If not established, ignore
that "block start data", and then execute the next point's "block start data".
Carry out the condition judgment set in "condition data" for the designated positioning data, and
when the conditions are established, execute the "block start data". If not established, stop the
control (wait) until the conditions are established.
Simultaneous execute (output pulses at same timing) the positioning data with the No.
designated for the axis designated in the "condition data".
Up to four axes can start simultaneously.
Repeat the program from the block start data with the "FOR loop" to the block start data with
"NEXT" for the designated No. of times.
Repeat the program from the block start data with the "FOR condition" to the block start data
with "NEXT" until the conditions set in the "condition data" are established.
Set the end of the repetition when "05
(FOR condition)" is set.
Refer to Chapter 10 "High-level Positioning Control" for details on the control.
Setting details
Da.12
Start data No.".)
Setting details
: Repetition start (FOR loop)" or "06
H
5 - 78