Event input assignment 1

Event input assignment
2
• When one E53-AKB unit is mounted, only "Event input assignment 3" and
"Event input assignment 4" can be used.
• This parameter specifies event input other than the multi-SP function. The fol-
Function
lowing four functions can be specified:
Run/Stop, Remote/Local, Auto/Manual, SP mode.
The Remote/Local function can be used on E53-AK01/02/03 option units. The SP
mode functions can be used only when the "Remote SP enable" parameter is ON.
• Event input (Run/Stop, Manual/Auto, and SP mode) is disabled while the menu is
displayed.
It is also disabled in set up, expansion, option and calibration modes.
Symbol
Comment
• Default
Event input assignment 1
Event input assignment 2
Event input assignment 3
Event input assignment 4
F Related article
4.3 How to Use Event input (page 4-8)
F Related parameters
See
"remote SP enable" "multi-SP function" (option mode)
F Option unit
E53-AKB
Model
Function
Not specified
Run/Stop
Remote/Local
Manual/Auto
SP mode
E53-AKB×1
Option Mode
Event input assignment
3
Event input assignment
4
Conditions of Use
Event input other than the multi-SP func-
tion must be specified when the event
input function is in use.
Event Input Operation
Event input disabled
ON: Stop/OFF: Run
ON: Remote/OFF: Local
ON: Manual/OFF: Auto
ON: Remote SP/OFF: Local SP
E53-AKB×2
--
--
5--39