CHAPTER 5 PARAMETERS
Setup Mode

_C/_F selection

• This parameter can be used when thermocouple or platinum resistance thermom-
eter is selected as the input type.
• Set the temperature input unit to either of "_C" or "_F".
Function
Comment
F Related article
3.2 Setting Input Specifications (page 3-4)
F Related parameter
See
"Input type" (setup mode)
Control output 1
assignment
Control output 2
assignment
• Assigns the output functions to either of control output 1 or 2.
• The following seven output functions can be assigned as outputs:
Function
• Errors 1, 2 and 3 cannot be assigned as outputs.
• When the output function assigned to control output 1 is ON, the "OUT1" LED
lights. However, note that the OUT1 LED does not light when control output (heat)
or control output (cool) are assigned to linear outputs such as current and voltage.
• When the output function assigned to control output 2 is ON, the "OUT2" LED
lights.
Comment
Defaults:
"Control output 1" = [
F Related article
3.3 Setting Output Specifications (page 3-6)
F Related parameters
See
• Alarm-related parameters
• Heating and cooling related parameter
"LBA detection time" (level 2 mode)
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
Model
5--28
Setting Range
: _C /
: _F
Control output (heat), Control output (cool), Alarms 1 to 3, HBA, and LBA.
Symbol
Control output
Function
(heat)
Conditions of Use
The input type must be set to tempera-
ture input (thermocouple or platinum
resistance thermometer).
Default
Conditions of Use
The control must be standard control or
heating and cooling control.
Control output
Alarm 1 Alarm 2 Alarm 3
(cool)
], "Control output 2" = [
HBA
LBA
]