Position-Proportional Control; On/Off Control; Travel Time; Valve Opening Monitor - Omron E5AK User Manual

Digital controller
Hide thumbs Also See for E5AK:
Table of Contents

Advertisement

J Position-propor-
tional control
F Travel time
F Valve opening
monitor
F Manipulated vari-
able at stop/PV
error
F Other functions
• Use the position-proportional type controller for position-propor-
tional control.
• On a position-proportional type controller, control output 1 is used
for open output, and control output 2 is used for close output. Accord-
ingly, control outputs 1 and 2 cannot be used as output assignments.
Special output units are already set on position-proportional type
controllers.
• On a position-proportional type controller, the following functions are
disabled.
ST
MV limiter
P and PD control
40% AT
LBA
HBA

ON/OFF control

• The travel time is factory-set to "30 seconds."
• To change the travel time, either set in the "travel time" parameter
(option mode), or execute motor calibration in the "motor calibra-
tion" parameter (option mode).
• The valve opening can be monitored when a potentiometer is con-
nected to the controller. However, be sure to execute motor calibra-
tion after connecting the potentiometer.
• The monitored valve opening is displayed on the bar graph in 10%
increments.
• Open, close or hold can be selected as output at stop or PV error. Set
these outputs in the "manipulated variable at stop" or "manipulated
variable at PV error" parameters (level 2 mode).
• Set the dead band in the "position-proportional dead band" parame-
ter (level 1 mode).
• Set the open/close hysteresis in the "open/close hysteresis" parameter
(level 1 mode).
ON
OFF
-100%
4.1 Selecting the Control Method
Open/close hysteresis
Dead band
MV--Valve opening
0
100%
4--3