Transfer output type
Transfer output upper
limit
Transfer output lower
limit
• These parameters set the transfer output conditions.
• The "transfer output type" parameter selects one of the following as the transfer
output type, and assigns this to transfer output:
Function
Set point, Set point during SP ramp, Process value, Manipulated variable (heat)
(standard type), Manipulated variable (cool) (This can selected only during heat-
ing and cooling control on a standard type controller.), Valve opening (position-
proportional control)
• The "transfer output upper limit" and "transfer output lower limit" parameters
are used for scaling of transfer output. The setting range varies according to this
output data. Also, a lower limit value larger than the upper limit value may be set.
• During temperature input, the decimal point position of the set point, set point
during SP ramp or process value is dependent on the currently selected sensor,
and during analog input on the results of scaling.
[
Comment
[
[
[
[
[
• Default : [
• The output ranges of the set point, set point during SP ramp or process value
when temperature input is selected are the ranges supported by the selected sen-
sor.
• When you have selected the "manipulated variable (heat)" parameter, the transfer
output lower limit during heating and cooling control becomes "0.0".
F Related article
4.7 How to Use Transfer Output (page 4-17)
See
F Option unit
E53-AKF
Model
Transfer output Type
] Set point
] Set point during SP ramp
] Process value
] Manipulated variable (heat)
] Manipulated variable (cool)
] Valve opening
]
Option Mode
Conditions of Use
The transfer output function must be in
use.
Transfer Output Lower Limit to

Transfer Output Upper Limit

Set point lower limit value to Set point upper limit value
Set point lower limit value to Set point upper limit value
Scaling lower limit to scaling upper limit
-5.0% to 105.0% (Standard control), 0.0 to 105.0% (heating
and cooling control)
0.0% to 105.0%
-10.0 to 110.0%
5--41