CHAPTER 5 PARAMETERS
Level 1 Mode

Dead band

• Sets the output dead band width in a heating and cooling control system. A nega-
tive setting sets an overlap band.
Function
Comment
F Related article
4.1 Selecting the Control Method (page 4-2)
See
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
Model
Position-proportional
dead band
• Sets the output hold width during position-proportional control (ON/OFF switch-
ing point for open and close output).
Function
ON
OFF
Comment
F Related article
4.1 Selecting the Control Method/Position-proportional Control (page 4-3).
F Related parameter
See
"Open/close hysteresis" (Level 2 mode)
E5AK-PRR2 AC100-240
E5AK-PRR2 AC/DC24
Model
5--14
Setting Range
-19.99 to 99.99
-100%
Setting Range
0.1 to 10.0
Conditions of Use
The control system must be heating and
cooling control.
Unit
Default
%FS
0.00
Conditions of Use
Control must be position-proportional
control
Open/close hysteresis
Dead band
MV--Valve opening
0
Unit
Default
%
2.0