F Startup Conditions of DT
F Startup Conditions of HT
A--16
(1) DT will start if the temperature that has been stable varies due to ex-
ternal disturbance and the deflection of the temperature exceeds the
stable range, and then the temperature becomes stable, provided that
the number of maximum temperature values is less than four.
(2) DT will start if the set point is changed under the condition that
SRT does not start and the temperature becomes stable, provided
that the number of maximum temperature values is less than four.
If there are four or more maximum temperature values, HT will
start.
Temperature
SP
Extreme value 1
HT will be ON when there is hunting with four or more maximum tem-
perature values(extreme values) while SRT is not being executed.
Temperature
SP
Extreme
value 1
Note: In specific applications where temperature varies periodically due
to disturbance, internal parameters need to be adjusted.
Set point change
Extreme value 2
Extreme value 2
Extreme value 4
Extreme
value 3
Time
Time