CHAPTER 5 PARAMETERS
Option Mode

Remote SP enable

• When this parameter is set to "ON", the remote SP and local SP can be switched
for use. (That is, to the SP mode can be specified.). Also, the "set point during SP
ramp" parameter is enabled at all times.
Function
• When this parameter is set to "OFF", only the local SP can be used. The set point
during SP ramp is enabled only when the SP ramp function is enabled.
[
Comment
F Related article
4.4 How to Use the Remote SP (page 4-11)
F Related parameters
See
"Set point during SP ramp" (level 0 mode)
"SP mode" (level 2 mode)

Remote SP upper limit

Remote SP lower limit

• Sets the remote SP upper and lower limit values. The upper limit value is the
equivalent to 20 mA, and the lower limit value is equivalent to 4 mA. Set the
upper limit value in the "remote SP upper limit" parameter and the lower limit
Function
value in the "remote SP lower limit" parameter.
• When the "SP setting upper limit" or "SP setting lower limit" parameters are
changed, the remote SP upper and lower limit values are forcibly changed to the
SP setting upper and lower limit values.
5--44
Setting Range
]: Enabled/[
]: Disabled
RSP (%)
Upper limit value
Lower limit value
Conditions of Use
ST must be OFF.
Default
[
]
Conditions of Use
The remote SP function must be
enabled.
4
20
Input (mA)