F Event input
10
30
20
31 32
9
29
19
8
28
18
7
27
17
6
26
16
5
25
15
4
24
14
3
23
13
2
22
12
33
1
21
11
F Transfer output
F Communications
• Connect event inputs 1 and 2 (EV1/2) to terminal Nos.18 to 20, and
event events 3 and 4 (EV3/4) to terminal Nos.24 to 26. However, note
that terminal Nos.18 to 20 cannot be used on controllers having a
communications function.
• Connect the event inputs as follows:
EV1
20
EV2
19
COM
18
Event input 1 and 2
Terminals 18 and 24 (COM) are connected internally.
• Use event inputs under the following conditions:
Contact input
ON: 1 kΩ max., OFF: 100 kΩ min.
No-contact input
ON: residual voltage 1.5 V max.,
OFF: leakage current 0.1 mA max.
• Polarities during no-contact input are as follows:
+
EV1
20
+
EV2
19
COM
18
--
Event input 1 and 2
• Connect transfer output (TRSF) to terminal Nos. 29 and 30.
• The internal equalizing circuit for transfer output is as follows:
4 to 20mA
• Transfer output specifications are as follows:4 to 20 mA,
Permissible load impedance: 600 Ω max.,
Resolution: Approx. 2600
• Terminal Nos.18 to 20, 31 and 32 can be used only on controllers hav-
ing a communications units (E53-AK01/02/03).
• For details on wiring, see Chapter 6, Using the Communications
Function.
+
+
EV3
26
+
+
EV4
25
COM
24
--
--
Event input 3 and 4
+
EV3
26
+
EV4
25
COM
24
--
Event input 3 and 4
+
30
L
29
- -
2.3 Wiring Terminals
2--11