CHAPTER 6 USING THE COMMUNICATIONS FUNCTION
Parameter No.
44
SP ramp time unit
45
SP ramp set value
46
LBA detection time
47
MV at stop
48
MV at PV error
50
MV upper limit
49
MV lower limit
51
MV change rate limit
56
Input digital filter
88
Open/close hysteresis
25
Alarm 1 hysteresis
26
Alarm 2 hysteresis
52
Alarm 3 hysteresis
53
Input shift upper limit
54
Input shift lower limit
57
Input type
59
Scaling upper limit
58
Scaling lower limit
60
Decimal point
30
_C/_F selection
61
Control output 1 assignment
62
Control output 2 assignment
63
Auxiliary output 1 assignment
64
Auxiliary output 2 assignment
65
Alarm 1 type
66
Alarm 1 open in alarm
67
Alarm 2 type
68
Alarm 2 open in alarm
69
Alarm 3 type
70
Alarm 3 open in alarm
71
Direct/Reverse operation
*1 During heating and cooling control, the range becomes -105 to 105.0. During position-proportional control, you can select
between
*1
0: Hold/1: Open/2: Close. (Default is 0: Hold.)
*2 During heating and cooling control, the range becomes 0.0 to 105.0.
*3 During heating and cooling control, the range becomes -105.0 to 0.0
*4 See page 5-26.
*5 0: Control output (heat), 1: Control output (cool), 2: to 4: Alarms 1 to 3, 5: HBA, 6: LBA, 7 to 9: Errors 1 to 3
*6 See page 5-30.
6--8
Parameter
Data Setting Range
0: Minutes, 1: Hours
0 to 9999
0 to 9999
-5.0 to 105.0
-5.0 to 105.0
MV lower limit +0.1 to 105.0
-5.0 to MV upper limit -0.1
0.0 to 100.0
0 to 9999
0.1 to 20.0
0.01 to 99.99
0.01 to 99.99
0.01 to 99.99
-199.9 to 999.9
-199.9 to 999.9
0 to 21
Scaling lower limit +1 to 9999
-1999 to scaling upper limit -1
0 to 3
0 : _C, 1 : _F
0 to 6
0 to 6
2 to 9
2 to 9
1 to 11
0: closed in alarm, 1: open in alarm
1 to 11
0: closed in alarm, 1: open in alarm
1 to 11
0: closed in alarm, 1: open in alarm
0: Reverse operation, 1: Direct operation
Mode
*1
*1
*2
*3
Level 2
*4
*5
*5
*5
Setup
Setup
*5
*6
*6
*6