Selecting The Operation Command - Omron SYSDRIVE 3G3MV SERIES User Manual

Sysdrive 3g3mv series multi-function compact inverter
Hide thumbs Also See for SYSDRIVE 3G3MV SERIES:
Table of Contents

Advertisement

Basic Operation
5-5

Selecting the Operation Command

The following description provides information on how to input operation commands to
start or stop the Inverter or change the direction of rotation of the Inverter.
Two types of command input methods are available. Select either one of them according
to the application.
H Selecting the Operation Mode (n003)
• Select the method of operation mode input to start or stop the Inverter.
• The following method is enabled in remote mode only. The command can be input through key
sequences on the Digital Operator.
n003
Operation Command Selection
Setting
0 to 3
range
Set Values
Value
0
The RUN and STOP/RESET Keys of the Digital Operator are enabled.
1
Multi-function input in 2- or 3-wire sequence through the control circuit terminals is enabled.
2
RS-422/485 communications are enabled.
3
Input from option (DeviceNet Communications Unit) is enabled.
H Selecting the STOP/RESET Key Function (n007)
• When parameter n003 is not set to 0, set whether or not to use the STOP/RESET Key of the Digital
Operator to stop the Inverter in remote mode. The STOP/RESET Key is always enabled in local mode
regardless of the setting in n007.
n007
STOP Key Function Selection
Setting
0, 1
range
Set Values
Value
0
The STOP/RESET Key of the Digital Operator is enabled.
1
The STOP/RESET Key of the Digital Operator is disabled.
5-10
Register
0103 Hex
Unit of
1
setting
Description
Register
0107 Hex
Unit of
1
setting
Description
Chapter 5
Changes during
No
operation
Default setting
0
Changes during
No
operation
Default setting
0