List of Parameters
Param-
Regis-
Name
eter
ter No.
No.
(Hex)
n175
01AF
Low-speed
carrier fre-
quency re-
duction selec-
tion
n176
01B0
Parameter
copy and
verify function
selection
n177
01B1
Parameter
read prohibit
selection
Note The default setting for 5.5-kW and 7.5-kW Inverters is "1."
Description
This function automatically reduces
the carrier frequency to 2.5 kHz if the
output frequency is 5 kHz or less, and
the output current is 110% or greater
than the rated Inverter current. Nor-
mally this setting is not necessary.
This function improves the overload
capacity at low frequencies.
0: Disables low-speed carrier fre-
quency reduction.
1: Enables low-speed carrier frequen-
cy reduction.
* Normally, it is not necessary to
change the default setting.
* This function is enabled if n080
(carrier frequency) is set to 2, 3, or
4.
Selects the function to read, copy,
and verify the parameter between the
memory of the Inverter and that of the
Digital Operator.
rdy: Ready to accept the next com-
mand.
rEd: Reads the Inverter parameter.
Cpy: Copies the parameter to the
Inverter.
vFy: Verifies the Inverter parameter.
vA: Checks the Inverter capacity
display.
Sno: Checks the software number.
Select the copy-prohibit function.
Set this parameter to store the data in
the EEPROM of the Digital Operator.
0: Read prohibited for Inverter param-
eters (data cannot be stored in
EEPROM).
1: Read possible for Inverter parame-
ters (data can be stored in
EEPROM).
Chapter 10
Set-
Unit
Default
Changes
ting
of
setting
range
set-
ting
0, 1
1
0 (See
No
note.)
rdy to
---
rdy
No
Sno
0, 1
1
0
No
Ref-
during
er-
opera-
ence
tion
page
6-24
3-10
3-17
10-33