Advanced Operation
Deceleration
The Inverter decelerates normally and is not in energy-saving control.
Power
consumption
Load rate: 50%

6-2-2 Performing Energy-saving Settings

n139
Energy-saving Control Selection
Setting
0, 1
range
Set Values
Value
0
Energy-saving control disabled
1
Energy-saving control enabled
Note 1. Set n139 to 1 to enable energy-saving control.
Note 2. Energy-saving control is enabled within a frequency range from 15 to 120 Hz and disabled if
the frequency exceeds 120 Hz.
n158
Motor Code
Setting
0 to 70
range
Note The default setting varies with the capacity of the Inverter model.
Set Values
• The motor code is used for automatically setting the energy-saving constant in n140.
• By setting the motor code, the value in n140 (energy-saving control coefficient K2) will change auto-
matically. To adjust energy-saving control coefficient K2, set the motor code in advance.
• Select the motor code from the following table based on the power supply voltage of the Inverter and
the capacity of the motor.
6-6
Load rate: 100%
Register
Unit of
setting
Description
Register
Unit of
setting
As shown in the graph, the voltage to
operate the motor most efficiently varies with
the motor load condition. The Inverter in
energy-saving control adjusts the output
voltage by using the ideal calculated value
so that the actual output power will be
minimum.
Motor voltage
018B Hex
Changes during
operation
1
Default setting
019E Hex
Changes during
operation
1
Default setting
Chapter 6
No
0
No
See note