List of Parameters
Para
Reg-
Name
me-
ister
ter
No.
No.
(Hex)
n066
0142
Multi-func-
tion analog
output
n067
0143
Multi-func-
tion analog
output gain
n068
0144
Multi-func-
tion analog
voltage
input gain
n069
0145
Multi-func-
tion analog
voltage
input bias
n070
0146
Multi-func-
tion analog
voltage
input filter
time con-
stant
n071
0147
Multi-func-
tion analog
current
input gain
n072
0148
Multi-func-
tion analog
current
input bias
n073
0149
Multi-func-
tion analog
current
input filter
time con-
stant
Description
Selects the monitor item with n065 set to 0.
0: Output frequency (with 10-V output at max.
frequency)
1: Output current (with 10-V output with
Inverter rated output current)
2: Main circuit DC voltage (with 10-V output at
400 [800] V DC)
3: Vector operation torque monitor (with 10-V
output at rated motor torque)
4: Output power (with 10-V output at power
equivalent to max. applicable motor capac-
ity) Cannot be monitored in vector control
mode.
5: Output voltage (with 10-V output at
200 [400] V AC)
* Values in ( ) apply with n067 set to 1.00.
* Values in [ ] are for 400-V models.
Used to set the output characteristics of multi-
function analog output.
Sets the input characteristics of multi-function
analog voltage input.
Gain:Sets the frequency of maximum analog
input (10 V) in percentage based on the
input (10 V) in percentage based on the
maximum frequency as 100%.
Bias: Sets the frequency of minimum analog
input (0 V) in percentage based on the
maximum frequency as 100%.
Sets a primary lag digital filter for multi-function
analog voltage input.
Sets the input characteristics of multi-function
analog current input.
Gain:Sets the frequency of maximum analog
input (20 mA) in percentage based on the
input (20 mA) in percentage based on the
maximum frequency as 100%.
Bias: Sets the frequency of minimum analog
input (4 mA) in percentage based on the
maximum frequency as 100%.
Sets a primary delay digital filter for multi-func-
tion analog current input.
Chapter 10
Set-
Unit
Defaul
Chan-
ting
of
t set-
ges dur-
range
set-
ting
ting
opera-
0 to 5
1
0
No
0.00
0.01
1.00
Yes
to
2.00
–255
1%
100
Yes
to 255
–100
1%
0
Yes
to 100
0.00
0.01 s 0.10
Yes
to
2.00
–255
1%
100
Yes
to 255
–100
1%
0
Yes
to 100
0.00
0.01 s 0.10
Yes
to
2.00
Ref-
er-
ing
ence
page
tion
5-38
5-38
5-16
5-16
5-17
5-16
5-16
5-17
10-19