List of Parameters
Param-
Regis-
Name
eter
ter No.
No.
(Hex)
n037
0125
Motor protec-
tion charac-
teristics
n038
0126
Motor protec-
tive time
n039
0127
Cooling fan
operation
n040
0128
Motor rotation
direction
10-8
Description
Used to set the motor overload detec-
tion (OL1) for the electronic thermal
characteristics of the motor.
0: Protection characteristics for gen-
eral-purpose induction motors
1: Protection characteristics for
inverter-dedicated motors
2: No protection
* If a single Inverter is connected to
more than one motor, set the
parameter to 2 for no protection.
The parameter is also disabled by
setting n036 for rated motor to 0.0.
Used to set the electric thermal char-
acteristics of the motor to be con-
nected in 1-minute increments.
* The default setting does not
require any changes in normal
operation.
* To set the parameter according to
the characteristics of the motor,
check with the motor manufacturer
the thermal time constant and set
the parameter with some margin.
In other words, set the value
slightly shorter than the thermal
time constant.
* To detect motor overloading
quicker, reduce the set value, pro-
vided that it does not cause any
application problems.
Used to operate the Cooling Fan of
the Inverter while the Inverter is
turned ON or only while the Inverter is
in operation.
0: Rotates only while RUN command
is input and for 1 minute after
Inverter stops operating
1: Rotates while Inverter is turned ON
* This parameter is available only if
the Inverter incorporates a Cooling
Fan.
* If the operation frequency of the
Inverter is low, the life of the fan
can be prolonged by setting the
parameter to 0.
0: A forward command rotates the
motor counterclockwise when
viewed from the load.
1: A forward command rotates the
motor clockwise when viewed from
the load.
Chapter 10
Set-
Unit
Default
Changes
ting
of
setting
range
set-
ting
0 to 2
1
0
No
1 to 60 1 min
8
No
0, 1
1
0
No
0, 1
1
0
No
Ref-
during
er-
opera-
ence
tion
page
6-39
6-39
6-40
---