Test Run
Key sequence
In approximately
1 s.
H Setting the Rated Motor Current
Parame-
Register
ter
n036
0124
Rated
motor
current
Key sequence
In approximately
1 s.
Indicator
Display
example
Name
Description
Used to set the rated motor
current (A) used for the ref-
erence current of motor
overload detection (OL1).
Note
1. The default set-
ting for the rated
motor current is
the standard rated
current of the
maximum applica-
ble motor.
Note
2. Motor overload
detection (OL1) is
disabled by set-
ting the parameter
to 0.0.
Indicator
Display
example
Explanation
The parameter number is displayed.
Use the Increment or Decrement Key to display "n002."
Press the Enter Key to display the set value in n002.
Use the Increment or Decrement key to set n002 to 0
unless the value is already set to 0, during which the
display flashes.
Press the Enter Key so that the set value will be entered
and the data display will be lit.
The parameter number will be displayed again in
approximately 1 s.
Setting
range
0.0% to
150%
(A) of
rated
output
current
of the
Inverter
Explanation
The parameter number is displayed.
Use the Increment or Decrement Key to display "n036."
Press the Enter Key to display the set value in n036.
Use the Increment or Decrement Key to set n036 to the
rated motor current, during which the display flashes.
Press the Enter Key so that the set value will be entered
and the data display will be lit.
The parameter number will be displayed again in
approximately 1 s.
Chapter 4
Unit of
Default
Chan-
setting
setting
ges dur-
opera-
0.1 A
See note
No
1 under
"Descrip-
tion.")
ing
tion
4-7