Basic Operation
Set Values
Value
Function
0
Forward/Reverse rotation
command
1
Forward/Stop
2
Reverse/Stop
3
External fault (NO)
4
External fault (NC)
5
Fault reset
6
Multi-step speed
reference 1
7
Multi-step speed
reference 2
8
Multi-step speed
reference 3
9
Multi-step speed
reference 4
10
Inching frequency
command
11
Acceleration/deceleration
time selection 1
12
External base block
command (NO)
13
External base block
command (NC)
14
Search command
(Searching starts from
maximum frequency)
15
Search command
(Searching starts from
preset frequency)
16
Acceleration/Decelera-
tion-prohibit command
17
Local or remote selection
18
Communications/Remote
selection
3-wire sequence (to be set in n052 only)
By setting n052 to 0, the set values in n050 and n051 are ignored
and the following settings are forcibly made.
S1: RUN input (RUN when ON)
S2: STOP input (STOP when OFF)
S3: Forward/Reverse rotation command
(OFF: Forward; ON: Reverse)
Forward rotation command in 2-wire sequence
Reverse rotation command (2-wire sequence)
ON: External fault (EFj detection: j is a terminal number)
OFF: External fault (EFj detection: j is a terminal number)
ON: Fault reset (disabled while RUN command is input)
Signals to select frequency references 2 through 16.
Note Refer to 5-6-4 Setting the Frequency References through Key
Note Refer to 5 6 4 Setting the Frequency References through Key
Sequences for the relationship between multi-step speed ref-
erences 1 through 4 and frequency references 1 through 16.
erences 1 through 4 and frequency references 1 through 16.
Note Any multi-step speed reference not set is regarded as turned-
OFF input.
OFF input.
ON: Inching frequency command (taking precedence over the
multi-step speed reference)
Refer to the description for set value 27.
ON: Output turned OFF (while motor coasting to a stop and "bb"
flashing)
OFF: Output turned OFF (with motor free running and "bb"
flashing)
ON: Speed search (Searching starts from n011)
ON: Speed search
ON: Acceleration/Deceleration is on hold (running at parameter
frequency)
ON: Local mode (operated with the Digital Operator)
Note After this setting is made, mode selection with the Digital Oper-
ator is not possible.
ON: RS-422/485 communications input is enabled.
Communications RUN command (0001 Hex) is enabled together
with frequency reference (0002 Hex).