Operation In V/F Control; Setting The Rated Motor Current (N036); Setting The V/F Patterns (N011 To N017) - Omron SYSDRIVE 3G3MV SERIES User Manual

Sysdrive 3g3mv series multi-function compact inverter
Hide thumbs Also See for SYSDRIVE 3G3MV SERIES:
Table of Contents

Advertisement

Basic Operation
5-3

Operation in V/f Control

This mode, which is used by conventional general-purpose inverters, is convenient
when replacing a conventional model with the 3G3MV Inverter because the Inverter in
this mode can be operated without considering the constants of the motor. Furthermore,
set the Inverter to this mode if the Inverter is connected to two or more motors or special
motors, such as high-speed motors.
To operate the Inverter in V/f control mode, be sure to set n036 for the rated motor cur-
rent and n011 through n017 for the V/f pattern.

5-3-1 Setting the Rated Motor Current (n036)

• Check the motor nameplate and set this parameter to the rated current.
• This set value is used for determining the electronic thermal characteristics to protect the motor from
overheating. The correct set value protects the motor from burning that may result from overloading.
n036
Rated Motor Current
Setting
0.0% to 150% (A) of rated output
range
current of the Inverter
Note 1. The default setting for this parameter is the standard rated current of the maximum applicable
motor.
Note 2. Motor overload detection (OL1) is disabled by setting the parameter to 0.0.

5-3-2 Setting the V/f Patterns (n011 to n017)

• Set the V/f pattern so that the motor output torque is adjusted to the required load torque.
• The 3G3MV incorporates an automatic torque boost function. Therefore, a maximum of 150% torque
can be output at 3 Hz without changing the default settings. Check the system in trial operation and
leave the default settings as they are if no torque characteristic changes are required.
n011
Maximum Frequency (FMAX)
Setting
50.0 to 400.0 (Hz)
range
n012
Maximum Voltage (VMAX)
Setting
0.1 to 255.0 [0.1 to 510.0] (V)
range
n013
Maximum Voltage Frequency (FA)
Setting
0.2 to 400.0 (Hz)
range
n014
Middle Output Frequency (FB)
Setting
0.1 to 399.9 (Hz)
range
Register
0124 Hex
Unit of
0.1 A
setting
Register
010B Hex
Changes during
operation
Unit of
0.1 Hz
Default setting
setting
Register
010C Hex
Changes during
operation
Unit of
0.1 V
Default setting
setting
Register
010D Hex
Changes during
operation
Unit of
0.1 Hz
Default setting
setting
Register
010E Hex
Changes during
operation
Unit of
0.1 Hz
Default setting
setting
Chapter 5
Changes during
No
operation
Default setting
See note
1.
No
60.0
No
200.0
[400.0]
No
60.0
No
1.5
5-7