Note 3. The following parameter set values cannot be copied if the Inverters are different to each
other in capacity.
n011 to n017: V/f setting
n036: Rated motor current
n080: Carrier frequency
n105: Torque compensation core loss
n106: Rated motor slip
n107: Motor wire-to-wire resistance
Note 4. Functions for 5.5-/7.5-kW Inverters cannot be copied to Inverters with different capacities.
H Verifying the Parameter Set Values (vFy)
• In order to verify that the copied parameter set values in the Inverter coincide with those in the
EEPROM of the Digital Operator, set n176 for parameter copy function selection to vFy.
Note The parameter set values can be verified provided that they are copied between the Inverters that
are the same in power supply specification and control mode (i.e., V/f or vector control).
D Procedure to Verify the Parameter Set Values
Key sequence
Indicator
Completes
or
Note 1. The above operation is interrupted when the STOP/RESET Key is pressed while the parame-
ter number or parameter set value is flashing because the parameter set value does not coin-
cide. "End" will be displayed. By pressing the Mode or Enter Key, the parameter number
(n176) is displayed again.
3-16
n108: Motor leakage inductance
n109: Torque compensation limit
n110: Motor no-load current
n140: Energy-saving control coefficient K2
n158: Motor code
Display
example
Power ON
Press the Mode Key repeatedly until the PRGM
indicator is lit.
Use the Increment or Decrement Key to display
"n176."
Press the Enter Key. Then "rdy" will be displayed.
Use the Increment Key to display "vFy."
Press the Enter Key so that the parameter set values
are verified, during which the display flashes.
If there is a parameter set value that does not coincide,
the parameter number will flash.
Press the Enter Key so that the corresponding set
value in the Inverter will flash.
Press the Enter Key again so that the corresponding
set value in the EEPROM of the Digital Operator will
flash.
Press the Increment Key so that verification will
resume.
When the set values have been all checked, "End" will
be displayed.
Press the Mode or Enter Key. The parameter number
(n176) will be displayed again.